Revised: 05/03/2013
Reference: UMA Procedures for testing inspection and Maintenance of Life Safety Equipment and Systems (dated 09-18-2003)
Purpose: To establish procedures for the periodic testing and inspection of life safety equipment on the University of Maine at Augusta and University College at Bangor. This information covers general care and routine service requirements, for specific guidance on a particular piece of equipment or system refer to the above reference, consult the appropriate service manual, or contact an authorized servicing technician.
Definitions:
- Life Safety Equipment/Systems: Emergency apparatus, either singular or in a system configuration that provide essential life safety services during an emergency evolution.
- Inspection: Is the visual examination of life safety equipment/system to verify that it appears to be in good operating condition and is free of physical damage.
- Maintenance: Is repair service, to include periodic inspection and testing required to keep the equipment/system in operative conditions at all times and provides for replacement of equipment/systems or components when they become unpredictable or inoperable.
Discussion:
- Life safety equipment/systems are rarely used and their state of readiness is not always obvious, yet their operability is paramount should they be called on in an emergency.
- Due to the scope of involvement, inspections can be accomplished by Facilities Management personnel or Security Guards at the prescribed intervals. This will be done from floor level by walking through protected areas and observing their material condition. Should equipment/system(s) be in questionable operability, the Facilities Management Office will be notified and required to take corrective action.
- Only qualified individuals or companies will perform maintenance tasks on life safety equipment/systems. The Director of Facilities Management will ensure all systems are maintained in accordance with established intervals.
Procedures:
1. These procedures shall cover:
A. Emergency Lighting
B. Portable Fire Extinguishers
C. Automatic Sprinkler Systems
D. Fixed Fire Suppression Systems
E. Fire Detection and Alarm Systems
F. Exit Signs
G. Fire Doors
H. Emergency Eye Wash Stations
I. Emergency LP Gas Shut-Offs
1.A. Emergency Lighting:
Monthly: Functional Test for a minimum of thirty (30) seconds shall be conducted on every emergency lighting system. This will include emergency exit signs and emergency lights.
Annually: Functional Test for a minimum of one and one-half hours duration shall be conducted on every emergency lighting system. Equipment shall be fully operational for the duration of the test. Where emergency lighting is provided by a prime motor-operated generator, a delay of no more than ten (10) seconds is permitted from the time normal building lighting goes out and emergency lighting comes on.
1.B. Portable Fire Extinguishers:
Monthly: Visual inspection or “quick check” to ensure fire extinguishers are
Available and will operate. This quick check shall include:
- Located in the designated space
- No obstruction to access or visibility
- Operating instructions on nameplate legible and facing outward
- Seals and tamper indicators not broken or missing
- Fullness determined by weighing or “hefting”
- Visual exam for obvious physical damage, leakage or clogged nozzle
- Pressure gauge reading or indicator in the operable range/position
- HMIS label in place
If any of the above conditions are detected, immediate corrective actions shall be taken. Contact the Facilities Management Office to initiate corrective measures. If items 4 or 7 are found, the fire extinguisher will be immediately taken out of service and replaced.
Annually: All extinguishers shall serviced by an authorized servicing technician and hydrostatically tested before being returned to service.
Record Keeping: Records shall be kept on the fire extinguisher tag. The tag will include a record of monthly visual inspections and the service technician’s information.
1.C. Automatic Sprinkler Systems:
Weekly: Gauges on dry, preaction, and deluge systems shall be inspected to ensure that normal pressures are being maintained.
Monthly: Gauges on wet systems shall be inspected to ensure good condition and that normal pressures are being maintained.
Quarterly: Alarm devices shall be inspected to verify that they are free of physical damage.
Annually: From floor level, sprinklers shall be inspected to include sprinklers, pipes, fittings, hangers, and braces. No signs of leaks, corrosion, foreign materials, paint or signs of physical damage should be present. Sprinklers shall also be inspected for proper orientation. There shall be no storage or obstructions within eighteen (18) inches of the sprinkler deflector. Concealed sprinklers do not require annual inspection. The spare sprinkler supply shall also be inspected for proper number and types of spare items and a proper wrench for change-out of sprinkler heads.
Testing: For additional details on testing, see the above cited reference. UMA Facilities Management contracts this service to be performed.
1.D. Fixed Fire Suppression Systems:
UMA fixed fire suppression systems are inspected semi-annually by a qualified servicing technician.
1.E. Fire Detection and Alarm Systems:
Weekly: For unmonitored systems for alarms, supervisory or trouble signals, check fuses, interface equipment, lamps and LEDs, and primary (main) power supply.
Monthly: Will include the following:
- Check of fire alarm equipment to ensure not damaged or inoperative
- Check fire alarm system power supply for normal operation
- Illuminate lamps and LED on fire alarm enunciator panels
- Check manual stations for obstructions
- Check detectors for damage or obstructions
- Conduct a load voltage test on dry cell (primary type) batteries serving fire alarm systems
Semi-Annually: Performed by servicing technician
Annually: Performed by servicing technician
1.F. Exit Signs:
All exit signs must be illuminated by a reliable light source. Externally and internally illuminated signs shall be visible in both the normal and emergency lighting mode. Exist signs should be inspected simultaneously with emergency lighting and may be recorded on the same form.
1.G. Fire Doors:
Annually: Perform a visual inspection:
- For door or panel damage
- To ensure door is firmly mounted in frame
- Closure to ensure proper operation and is able to completely close with sufficient force to make it latch
- For proper latch alignment and ability to maintain door closed
- Of hinges to ensure secure attachment to door and frame
- To ensure coordinators are securely attached and operate properly
- For any unapproved modifications to doors
Maintenance: Shall be performed periodically or as needed depending on door use and location. At a minimum the following service should be performed during annual inspections:
- Lubricate guides and bearings
- Operate doors on automatic hold devices quarterly to assure proper operation.
- Adjust closing devices as necessary to ensure door completely closes
1.H. Emergency Eye Wash Stations:
Semi-Annually: A trained member of Facilities Management shall conduct a thorough inspection and service all Protector I eye wash centers and Protector II auxiliary eye wash stations strategically located on campus. This service shall include:
- Complete drain and flush of each unit
- Inspection of all rubber nozzles
- Interior and exterior cleaning
- Refill with the proper ratio of solution and water
- Reaffix safety seal and document attached service card
1.I. Emergency LP Gas Shut-offs:
Annually: Facilities Management personnel will test operation of the Emergency LP gas shut-offs located in Jewett Hall. To avoid classroom disruption, this test will be performed during the regularly scheduled winter break. One shut-off control will be randomly selected to ensure proper operation of the control solenoid located by the door to each of the labs that contain LP gas. If adjustments are required, the servicing LP gas provider will be contacted.
Record Keeping: Written records must include the building, location of units within the building, date of monthly and/or annual test, results of test, and name of person conducting the test. These records must be retained for five (05) years.